- Megger residential wiring - Electrician Talk
A megger is simply a "megohm meter" and it only measures insulation resistance, at higher values than a regular ohm meter Generally a regular DMM operates at 9VDC on the ohm scale A megger will have selectable outputs of 50, 100, 250, 500, or 1000VDC to test insulation to ground or phase to phase as desired, at the proper voltage for the circuit under test It will not pin point the spot of
- megging a motor wired up - Electrician Talk
A megger is used to test the integrity of insulation If you are testing a motor circuit wired to a MCC bucket or a VFD; Open the breaker in the bucket or isolated the VFD Always test your Megger first with leads together and leads apart Clamp onto the equipment ground with one lead and one of the T-leads with the other
- Hi-Pot Vs Megger Testing - Electrician Talk
If you see a fault with the megger, you will see a fault with the hipot The hipot stresses the insulation weak points at higher voltage levels than the megger will I don't think the hi pot will do anything for you except maybe create an unwanted fault flash over Are the motors delta?
- Megging wire results - Electrician Talk
Megging motors and conductors can be dangerous Even after a megger has been removed from the circuit the wires may have stored energy Conductors that are isolated from equipment on both ends will act as a capacitor and store the energy the megger put into it If you touch that conductor, the stored energy will get your attention
- What are acceptable Megger readings with 1000v testing. . .
You normally use 2x the rated voltage for megger testing A 240V motor would be tested at 500V, not 1000V Higher voltages are the province of hi-pot testing, which is normally done to failure when testing samples of a product
- Megger or multimeter - Electrician Talk
When we need to check Motor, Megger is used, why cant we use mutilmeter continuity to check the motor ??? Why megger is must?? cant Multimeter replace it?? what are the disadvantages of using multimeter for motor checking???
- Testing wiring with a megger - Electrician Talk
Are there any resources for testing wiring with a megger? An example is to test wiring in a home which reads clear in terms of continuity but trips an arc fault under load Another example is to certify that a wire is in safe working condition unquestionably I'm currently using the Fluke 1507
- Megger - Electrician Talk
Megger readings that do not stabilize, but fluctuate are indicative of moisture in or on the conductors and should be investigated Sometimes this reading will continue to climb as the moisture evaporates due to the test voltage When meggering one must be careful with the voltage levels you are trying to prevent future electrical damage to
|
|
|